To change the tap position of a 3-winding transformer during a simulation define a parameter event (EvtParam) using the appropriate variable: e:nntap_int_h which corresponds to the tap-position HV…
Yes, it is possible to exchange variables between two composite models in the same way as it is done between two common models. It is only necessary to set up a frame in which the two frames are…
A common application for BESS consists in replacing the spinning reserve/primary reserve in a power system. This application becomes significantly important in small or island power systems with…
The idea of the initialisation is to preset the internal model signals by the results of an initial load flow.The key point is to first check for each DSL-model, which inputs/outputs are known and…
There are several possibilities to calculate the initial conditions. Consider the example y=a*u+b, where y is the output and u the input signal of the model. The initial value of y is known (=0),…
To simulate a load event you have to use the EvtLod. The load event works as follows:1. Incremental change Certain percentage of current value, P = P + P*dP/100 (same for Q)2. Absolute change Absolute…
A static load model is always equivalent to a constant impedance model. For modelling any different characteristic, you have to switch it over to 100 percent dynamic. A real constant PQ load model can…
The example attached includes a measurement file drive in a 3-phase load. Import the project, save the data file loadmeas.txt to the hard disk and select this file in the measurement file object of…
In the attached example a random signal is generated using the sample and hold noise generator (ElmNoise) within a DSL model. The generated random signal is defined to change every 1/Frequency…
The slots in the standard frames are predefined slots for the different elements a synchronous machine controller may have, i.e. the element Power System Stabilizer (ElmPss), etc. The names of the…