How can I adjust the tap positions of a 3-winding transformer during the simulation?
Category:
            Dynamic Simulation
        Answer
            To change the tap position of a 3-winding transformer during a simulation define a parameter event (EvtParam) using the appropriate variable:
- e:nntap_int_h which corresponds to the tap-position HV side.
- e:nntap_int_m which corresponds to the tap-position MV side.
- e:nntap_int_l which corresponds to the tap-position LV side.
The attached project includes an example.