How to model the frequency dependent norton equivalent of a static generator or PV system?
Frequency dependent characteristics of the reactances and resistances (in p.u.) can be define for the static generator, see at ‘Harmonics/Power Quality’ page and ’Frequency Dependencies’ tab.
Several types of characteristics can be applied to the resistances and reactances:
- Frequency Polynomial Characteristic (ChaPol)
- Vector Characteristic (ChaVec)
- Matrix Characteristic (ChaMat)
- Operational Dependent Frequency Characteristic (ChaOpfreq),
The attributes of reactances and resistances r1(f), x1(f) … are in per unit. The characteristic will impact this attribute. According to the Usage of the characteristic, the equation are as follow.
Relative Usage:
r1(f) = r1h(fn) ・ fcharr1(f)
x1(f) = x1h(fn) ・ fcharx1(f)
r2(f) = r2h(fn) ・ fcharr2(f)
x2(f) = x2h(fn) ・ fcharx2(f)
r0(f) = r0h(fn) ・ fcharr0(f)
x0(f) = x0h(fn) ・ fcharx0(f)
relative % Usage:
r1(f) = r1h(fn) ・ fcharr1(f)/100
x1(f) = x1h(fn) ・ fcharx1(f)/100
r2(f) = r2h(fn) ・ fcharr2(f)/100
x2(f) = x2h(fn) ・ fcharx2(f)/100
r0(f) = r0h(fn) ・ fcharr0(f)/100
x0(f) = x0h(fn) ・ fcharx0(f)/100
absolute Usage:
r1(f) = fcharr1(f)
x1(f) = fcharx1(f)
r2(f) = fcharr2(f)
x2(f) = fcharx2(f)
r0(f) = fcharr0(f)
x0(f) = fcharx0(f)
A Parameter Characteristic (ChaVec) with absolute usage will replace the the attribute directly and the unit of the characteristic values must match with the assigned attribute.
In case of a Static Generator (ElmGenstat) or a PV-System (ElmPvsys) or a STATCOM (ElmStatcom) the values in the tabular of the characteristic (ChaVec) need to be in per unit when using the "absolute" usage.
Attached to this article, there is an excel file with an example, how you come from a R and X characteristic in Ohm to the input values for different model options in PowerFactory. In addition, there is a pfd model with the modeled example. After running the Frequency Sweep it can be seen, that all models have the same R(f) and X(f) plot.