How to calculate a single phase to ground Short Circuit throught a protective earth wire?
Category:
Short-Circuit
Answer
There are two ways to calculate this kind of fault:
- Use a 4-wire model in which the N-conductor is explicitly modelled and the PE-wire is reduced and modelled as earth. Then when calculate a phase to ground Short-Circuit, the phase to PE-wire is reproduced.
- The second option is to use a model with the PE-wire explicitly modelled, as an additional single-phase model. For this approximation is necessary to add an auxiliary node for IEC/VDE SC calculation.
In the attached example note that the result for both approximations is the same.