How can I simulate a network with unsymmetrical voltages and different phase impedances?
Category:
            Power Equipment Models
        Answer
            Attached you find an example with 3 unsymmetrical voltage sources.
It is required to use 3 symmetrical voltage sources and to connect them to the load busbar using 3 single-conductor cables (phase A of the first voltage source, phase B of the second and phase C of the third)
This procedure also works for dynamic simulations, although the control algorithm needs to be defined and implemented separately.