How can I control the negative sequence current of the static generator?

Category:
Dynamic Simulation
Answer

The static generator allows to control the negative sequence currents via the input signals i2d_ref and i2q_ref. Internally is the cosref, sinref signal used for the transformation (which is typically the positive sequence voltage angle). Therefore a compensation is needed to get "real" negative sequence input signals. The attached project contains an example which shows the application of such a transformation.

The composite model "ElmGenstat_for_neg_seq_control" can be used in slots instead of the static generator, via this the positive and negative sequence currents can be controlled.