There are two possibilities to work with user defined variables in a dynamic simulation: 1. Using the option ’User Defined Signal’ included within the VisPlot. This allows calculation of additional…
You will need to perform an EMT-type simulation for this purpose. To replicate the fault on the cable insulation, the cable must be explictly divided in two sections at the point where the faulty…
In the attached example the output power of a single phase load is controlled via an external file element (ElmFile). Import the project, save the text file to the hard disk and select this file in…
For load flow calculation, static analysis, the three phase voltages can only be altered by specifying the amplitude and the phase lag in the positive, negative and zero sequence system of the voltage…
For RMS simulations the load type has to be set to 100% dynamic load, this means constant impedance Z. Additionally in the RMS dialogue of the load type the voltage dependency of P and Q can be set.…
The attached project contains a small DPL example, where a controller will be created for asynchronous machines (ElmAsm). The DPL script is located inside the Scripts library. 1. Optionally it will…
A lightning event can be modelled in PowerFactory in two ways: using the built-in impulse source element (ElmImpulse) - recommended approach. using a detailed, user defined DSL model. The first method…
An example is provided attached depicting a linear and a non-linear dynamic load model.…
In the attached PowerFactory project, a current source is configured to inject fundamental frequency and harmonic currents into the system. The simple network model contains a current source which is…
Refer to the attached example. It describes an induction generator with the necessary dynamic models. The reactive power is balanced using a switched capacitor. The dynamic models are a shaft model…