Your search returned 30 items.
The options available are the following: Voltage  Measurement Device and Current Measurement Device (StaVmea and StaImea). These elements implement the measurement of time-dependent data of a…
Yes, it is possible to exchange variables between two composite models in the same way as it is done between two common models. It is only necessary to set up a frame in which the two frames are…
The idea of the initialisation is to preset the internal model signals by the results of an initial load flow.The key point is to first check for each DSL-model, which inputs/outputs are known and…
In the attached example a test grid is used to shown an example configuration for a FFT (Fast Fourier Transformation) element. The example includes two Composite Models one using a three phase FFT…
You will need to perform an EMT-type simulation for this purpose. To replicate the fault on the cable insulation, the cable must be explictly divided in two sections at the point where the faulty…
For RMS simulations the load type has to be set to 100% dynamic load, this means constant impedance Z. Additionally in the RMS dialogue of the load type the voltage dependency of P and Q can be set.…
A simple moving average discrete time filter is provided for your reference. It can be used for both RMS and EMT type simulations. The register model (ElmReg) could be used to calculate a moving…
A lightning event can be modelled in PowerFactory in two ways: using the built-in impulse source element (ElmImpulse) - recommended approach. using a detailed, user defined DSL model. The first method…
Refer to the attached example. It describes an induction generator with the necessary dynamic models. The reactive power is balanced using a switched capacitor. The dynamic models are a shaft model…
In the attached PowerFactory project, a current source is configured to inject fundamental frequency and harmonic currents into the system. The simple network model contains a current source which is…