Your search returned 15 items.
For being able to consider frequency dependent network impedances you may use the Voltage Source element (ElmVac) or the External Grid element (ElmXnet). On the Harmonics-page, frequency…
To assign a spectrum to the load element, firstly add a load type to the load element and then set the model to current source. The spectrum must be defined and assigned under the Harmonics page of…
An ideal symmetrical system has the following phase shifts for harmonics of the nth order:A: 0°B: -n*120°C: n*120°For the third harmonic, for example, the phase shifts amount to:A: 0°B: -360°C:…
In the attached project (RippleControl.pfd) two different methods of modelling ripple control systems are illustrated: The study case "Serial Infeed" shows the simplified way by just inserting a…
There are two ways to simulate the harmonic voltage distortion from the feeding grid: To model the infeed as a voltage source and entering the harmonics on the Harmonics page. To model the infeed as…
The PWM converter model can either represent a harmonic current source or a harmonic voltage source. If you select the option "Constant I", the specified harmonic spectrum is injected as harmonic…
Assuming a harmonic voltage measurement is present and needs to be converted into current injections, the following steps need to be taken:1. Convert the measurement data from phase voltage…
The Thevenin and Norton equivalents are characterized by their open-circuit voltage and short circuit current. The inner voltage source of the Thevenin equivalent equals the open circuit voltage,…
The transformer impedance is mainly influenced by the series leakage inductance and copper losses for harmonic studies based on Harmonic Load Flow Calculation and Network Impedance Frequency Sweep…
The injection of harmonic currents is modeled in PowerFactory using the "Harmonic Sources" object (class "TypHmcur"). Various PowerFactory elements can be configured as harmonic current sources, such…