Protection Functions

The basic functional model library of DIgSILENT PowerFactory’s protection analysis tool has been extended to include additional devices such as CTs, VTs, relays, fuses and more complex protection schemes including user-defined modelling capabilities. Additionally, there are specially designed interactive VIs (Virtual Instruments) for displaying system quantities and, more importantly, for modifying protection settings in the graphical environment. This last feature is especially useful, as coordinated settings between different protection schemes can be modified via the cursor in the graphical environment, following which the settings in both the database and the simulation environment are also updated.

All protective devices are fully-functional under steady-state and transient conditions, allowing device response assessment under all possible simulation modes, including load flow calculation, fault analysis, RMS and Instantaneous Values (EMT) simulation.

PowerFactory’s main protection features are:


Protection Model Library and Functionality

The DIgSILENT PowerFactory protection analysis tool contains a comprehensive protection device model library. All relays are modelled for steady-state calculations (short-circuit, load flow), RMS and EMT simulation modes. The definition of relay types is highly flexible via block diagrams. For RMS and EMT simulation purposes, relays may be extended and adopted to cope with user specific requirements via the PowerFactory DSL language The features of the protection model library are listed below.

Fuses are represented by their melting curves. It is possible to take minimum and maximum melting curves into account.

Time-Overcurrent Relays for 1-phase, 3-phase, ground and negative sequence time over-currents. Additionally, the relay characteristics can incorporate the following standards and solution methods:

Instantaneous Overcurrent Relays for 1- phase, 3-phase, ground and negative sequence time over-currents.

Directional Relays for overcurrent, power, ground current, and any combination of time and instantaneous overcurrent relays. Additionally, voltage and current polarization is used for the detection of negative and zero sequence components considering also dual polarization. Optional: with voltage memory.

Distance Relays for phase, ground and zone distance protection. Provision is available for incorporating overcurrent and under-impedance starting units (U-I or Z) as well as angle under-impedance.

Different characteristics are available for distance relay zones including:

Support of various polarizations such as:

Zero sequence and parallel line compensation

Voltage Relays for under-voltage, instantaneous voltage, voltage balance and unbalance.

Additional devices such as: Breaker Fail, Motor Protection, Generator Protection, Differential Protection, Reclosing Relays, Low Voltage Circuit Breakers, and Out-of-Step Relays.


In addition to these protection functions and relays, DIgSILENT PowerFactory provides further devices and characteristics for more detailed protection system modelling, such as:

All protection device models are implemented within the composite model frame environment. This allows users to easily design and implement their own models, by utilizing the graphical user interface for constructing block diagrams.


Output & Graphical Representation

Time-Overcurrent Diagrams

R-X Characteristic Diagrams

Time Distance Diagrams

Single Line Diagram

Relay Setting Report

Relay Tripping Report


Overcurrent-Time Protection

The coordination of overcurrent-time protection is performed graphically using the current-time diagram as the basis. Relay settings are modified using drag & drop to move characteristics. Short-circuit currents calculated by the short-circuit command, are shown in the diagram as a vertical line. In addition, the corresponding tripping times of the relays are displayed. Coordination between relays at different voltage levels is available. Therefore, currents are automatically based on the leading voltage level, which can be selected by the user.


Distance Protection

For distance protection coordination, two powerful graphical features are integrated. The first of these features is the R-X diagram for displaying the tripping zone of distance relays and the line impedances. Several relays can be visualized in the same R-X diagram. This can be useful for the comparison of two relays that are located at different ends of the same line. The relay characteristics and the impedance characteristic of the connecting line will be shown in the same R-X diagram. Following short-circuit calculations, the measured impedances are visualized with a marker in the shape of a small arrow or cross. From the location of the marker the user can see the tripped zone and its associated tripping time. For dynamic simulation, measured impedances of the relays can be displayed, thereby visualizing the functioning of power swing blocking or out-of-step tripping relays.

The second powerful graphical feature is the time-distance diagram, which is used for checking the selectivity between relays along a coordination path. The relays on a coordination path can be displayed in diagrams for forward, reverse or for both directions. Consequently, it is very easy to check the selectivity of the relays along a coordination path. Two different methods for calculation of the tripping curves are provided. These are the kilometric and the short-circuit method.

A special feature of the distance protection is the consideration of blocking signals or POTT (permissive over-reach transfer tripping), PUTT (permissive under-reach transfer tripping), which are also taken into account. In addition to tripping curves of distance relays, the curves of overcurrent relays can be displayed and coordinated in the same diagram using the short-circuit method.

Both the kilometric and the short-circuit method consider breaker opening times in the calculation of tripping times. The breaker opening time can be optionally ignored.


Protection Coordination Wizard

The Protection Coordination Wizard for automatic overcurrent protection relay settings calculation is used to:

The Protection Coordination Wizard has the ability to verify/calculate the selectivity for each protective device using the settings of:

In order to protect the system, the rules implemented in the wizard calculate the relay settings of:

DIgSILENT PowerFactory

Educational Versions

Application Examples


PowerFactory 14.0 Flyer


PowerFactory 14.0 Brochure



DIgSILENT Overview Diagram